Second Order Control System
For a second-order control system, the undamped natural frequency (Īâ) and damping ratio (Îļ) are usually calculated from the characteristic equation.
1. Standard Second-Order System Form
The standard form of a second-order system is:
s² + 2ÎļĪâ s + Īâ² = 0
Where:
- Īâ = Undamped natural frequency (rad/s)
- Îļ = Damping ratio
- s = Laplace variable
2. How to Calculate from a Given Equation
If the characteristic equation is:
s² + a s + b = 0
Compare it with:
s² + 2ÎļĪâ s + Īâ²
Then:
Undamped Natural Frequency
Īâ = √b
Damping Ratio
Îļ = a / (2√b)
3. Example
Given:
s² + 6s + 25 = 0
Compare with standard form.
Step 1: Find Īâ
Īâ = √25 = 5 rad/s
Step 2: Find Îļ
Îļ = 6 / (2 × 5)
Îļ = 0.6
4. Final Answer
- Undamped Natural Frequency (Īâ) = 5 rad/s
- Damping Ratio (Îļ) = 0.6
5. Shortcut Formula
Īâ = √(constant term)
Îļ = coefficient of s / (2√(constant term))